CONTROL BOX 3S io
P21
Closing slowdown zone
P22
Opening slowdown zone
Values
0: zero slowing, only on Ixengo L 24V
1: shortest slowdown zone
to
5: longest slowdown zone
Default value:
- Control Box 3S Axovia: 1
- Control Box 3S Ixengo: 2
- Control Box 3S Axovia 200 io: 3
Warning
Comments
If parameters P21 or P22 are changed, the
installer must check that the obstacle detection
complies with appendix A of standard EN 12
453.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
P23
M1/M2 shi when closing
P24
M1/M2 shi when opening
Values
0: zero shi , only on Ixengo L 24V
1: minimum shi
to
10: maximum shi
Adjusted at the end of auto-programming
Warning
Comments
If parameters P23 or P24 are changed, the
installer must check that the obstacle detection
complies with appendix A of standard EN 12
453.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
1: Minimum shi ensuring the leaves do not cross.
Prohibited if hinged gate with 1 "covering" leaf.
10: maximum shi corresponding to the complete
movement of one leaf then the other
P25
M1 closing torque limitation
P26
M1 opening torque limitation
P27
M1 closing slowdown torque limitation
P28
M1 opening slowdown torque limitation
P29
M2 closing torque limitation
P30
M2 opening torque limitation
P31
M2 closing slowdown torque limitation
P32
M2 opening slowdown torque limitation
Values
1: minimum torque
to
10 (Axovia) or 20 (Ixengo): maximum torque
Adjusted at the end of auto-programming
Warning
Comments
If parameters P25 to P32 are changed, the
installer must check that the obstacle detection
complies with appendix A of standard EN 12
453.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
If the torque is too low, there may be erratic obstacle
detection.
If the torque is too high, the installation may not comply
with the standard.
Copyright
©
2017 SOMFY ACTIVITES SA. All rights reserved.
P37
Wired control inputs
Values
0: complete cycle mode - pedestrian cycle
1: opening mode - closing
Comments
0: terminal 30 input = complete cycle, terminal 32 input
= pedestrian cycle
1: terminal 30 input = opening only, terminal 32 input =
closing only
P39
Additional thrust when closing
Values
0: no thrust
1: with thrust (thrust of 2.5 sec a er detection of end
limit)
Comments
This parameter is only available on the Control Box 3S
models on Ixengo L 24V.
It must only be activated if the stops are installed on the
ground.
P40
Coupling speed when closing
P41
Coupling speed when opening
Values
1: slowest speed
to
4: fastest speed
Default value:
- Control Box 3S Axovia: 2
- Control Box 3S Ixengo: 2
- Control Box 3S Axovia 200 io: 1
Warning
Comments
If parameters P40 or P41 are changed, the
installer must check that the obstacle detection
complies with appendix A of standard EN 12
453.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
8. PROGRAMMING THE REMOTE CONTROLS
Key to the figures
A = "source" remote control already memorised
B = "target" remote control to be memorised
8.1. General information
8.1.1. Remote control types
There are two types of remote control:
• unidirectional: Keygo io, Situo io, Smoove io
• bidirectional with information feedback function (remote controls
indicate the movement in progress and issue confirmation of cor-
rect operation): Keytis io,Telis 1 io, Telis Composio io, Impresario
Chronis io
8.1.2. Memorising the remote controls
There are two ways to memorise a remote control:
• Memorising via the programming interface.
• Memorising by copying a previously memorised remote control.
Each control button is memorised individually.
Memorising a button which has already been memorised will clear this
button's function.
EN