Temperature sensor with overheating protection
Connect the cable to the temperature sensor's plug, see figure.
Screw the temperature sensor onto the wall, see figure.
The temperature sensor cannot be placed above the heater, it
must be at least 50 cm away from it.
The temperature sensor must be 15-20 cm from the ceiling.
The temperature sensor must be at least 50 cm from any air
opening (ventilation, door, window).
Vaporiser
A vaporiser is connected to outputs SL SN as shown in the
figure. If a vaporiser is connected, a vaporiser function must
also be selected from the control console settings. See User
instructions.
CAUTION!
When connecting the control console with an electrical
heater with vaporiser function ensure that the water tank is always
filled with water. When the water tank is empty, the vaporiser function
is disabled and there is a risk that the heating element my burn out.
Connection of a lighting system
Lighting/ventilation can be connected to the outputs LL LN of the
control console as shown in the figure. In that case it is possible
to switch on/off the connected lighting/ventilation system from
the control console.
To use a lighting function, the lighting function must be selected
from the control console settings. See User instructions.
The maximum power of the lighting/ventilation system is 230V
100W 50Hz.
8
6
7
4