Technical Data V-Uk And V-Mk - meibes BigFixLock Documentation Technique Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. Pump groups DN25 / DN32 / DN32+

7.3 Technical data V-UK and V-MK

Technical data: Pump groups V-UK DN 25 and 32
DN
top connection
bottom connection
Axis-Centre distance
Components made from
Dimensions per line
Sealant materials
Temperature display
Operating temperature
Operating pressure
Note: Change of side is possible before supply and return for UK.
Technical data: Pump groups V-MK DN 25 and 32
DN
top connection
bottom connection
Axis-Centre distance
Components made from
Dimensions per line
Sealant materials
Temperature display
Operating temperature
Operating pressure
k
– value mixer
VS
Performance overview / flow rates for V-UK
Dimension
DN 25
Top connections
1" female thread
Bottom connections
1 ½" male thread
Max. pressure rating
PN 10
Max. temperature
110°C
k
– value
7.2 m³/h
VS
P
V
Alpha 2 (L)
75/55
2.15
Magna3
115/77
3.3
Yonos Pico
70/46
2
Stratos Para
108/72
3.1
Output P [in kW] at ∆T 30K/ 20K; ∆T [in K] is the temp. differential between the supply line and return line. E.g. 85°C – 55°C = 30K
maximum flow rate V [in m³/h] at approx. 2 mWS residual delivery head
ATTENTION: The flow rate is determined by the respective pump that is used!
44
25
G 1" female thread
G 1 1/2" AG (flat seal)
from 175 mm upwards
steel, brass, EPP insulation
approx. height 550 x width 175 x depth 240 mm
PTFE, asbestos-free fibre seal, EPDM
0 to 120 °C
up to 110 °C
PN 10
25
G 1" female thread
G 1 1/2" AG (flat seal)
from 200 mm upwards (other distances available subject to a surcharge)
steel, brass, EPP insulation
approx. height 550 x width 175 x depth 240 mm
PTFE, asbestos-free fibre seal, EPDM
0 to 120 °C
up to 110 °C
PN 10
7.4
DN 32
DN 32+
1 ¼" female thread
1 ¼" female thread
1 ½" male thread
1 ½" male thread
PN 10
PN 10
110°C
110°C
7.6 m³/h
11.7 m³/h
P
V
P
V
75/55
2.15
89/59
2.55
118/79
3.4
178/119
5.1
70/46
2
84/56
2.4
108/72
3.1
129/86
3.7
32
G 1 1/4" female thread
32
G 1 1/4" female thread
7,4
Performance overview / flow rates for V-MK
Dimension
DN 25
Top connections
1" female thread
Bottom connections
1 ½" male thread
Max. pressure rating
PN 10
Max. temperature
110°C
k
– value
5.8 m³/h
VS
P
V
Alpha 2 (L)
46/23
2
Magna3
105/70
3
Yonos Pico
44/22
1.9
Stratos Para
97/65
2.8
Output P [in kW] at ∆T 20K/ 10K; ∆T [in K] is the temperature differential between the supply line and return line. E.g. 50°C – 30°C = 20K
maximum flow rate V [in m³/h] at approx. 2 mWS residual delivery head
32+
32+
12
DN 32
DN 32+
1 ¼" female thread
1 ¼" female thread
1 ½" male thread
1 ½" male thread
PN 10
PN 10
110°C
110°C
5.1 m³/h
9.8 m³/h
P
V
P
V
46/23
2
57/28
2.45
105/70
3
164/109
4.7
66/44
1.9
84/56
2.4
97/65
2.8
125/84
3.6

Publicité

Table des Matières
loading

Table des Matières