6. Boiler guard

The boiler guard (see „boiler guard" technical information) can be connected directly to the distributor, or the angle connection depending
on the size and/or pumped quantity. For this, reduction couplings are offered. This way, the distribution system can be put together as
needed. Housing: welded round container with adapter props made from a seamless steel tube incl. a BigFixLock groove. In the base there
is an opening for cleaning is with a 1" drain valve. The 3/4 „sleeves in the ground are used to pick up magnetite separators, which are
sealed with plugs, if none are needed. An automatic floating vent, a rinsing ball cock and a pocket immersion sleeve for accommodating
the temperature sensor are located in the lid. The boiler guard is held in place by a foot. Supplied with EPP - block insulation.
Max. permissible pressure rating: PN 6 / Max. permissible temperaturer: 110 °C
*Note: The intermediate pipes of the foot are to be shortened to the required length to adjust the height of the manifold or boiler guard.
40
A Rinsing tap with a hose fitting (included)
B Settling chamber
C Immersion sleeve for the temperature sensor
D Flow straightener
F Perforated plates
G Dividers
H Sludge pot
I
Drain ball valve with a hose fitting (included)
J Magnetite separator
L Impact plate
M Automatic floating vent