5. Distributors

The distributors consist of two stacked chambers with thermal separation of the supply and return lines. The boiler circuit is both connec-
table on the left and right hand side. All connections are prepared so that BigFixLock clamps can be used. The top outlets for connecting
the heating circuits are designed with BigFixLock groove in the nominal width DN 50 (Ø 60.3 mm). All distributors are painted, pressure
tested, fully insulated and supplied with two feet*. Furthermore, 2 couplings and 2 end caps are supplied with a 1/2" drill hole as well as
insulation for the clamps. The holes are sealed with plugs. Alternatively, a KFE-cock can be screwed on for emptying. The distributor sys-
tem consists of elements for two or three heating circuits, which can be combined as desired, depending on the axis-centre distance.
max. permissible pressure rating: PN 10 / max. permissible temperature: 110 °C

5.1 Distributors for 2 heating circuits

Art. no.
Pump volume
up to
66457.0
12 m³/h
66457.2
30 m³/h
66457.4
50 m³/h
66457.6
100 m³/h
* at ΔT = 20 K
*Note: The intermediate pipes of the foot are to be shortened to the required length to adjust the height of the manifold or boiler guard.
Power output
Ø pipe (AD)
up to*
in mm
280 kW
114.3
700 kW
168.3
1150 kW
168.3
2300 kW
219.1
Installation length 1135 mm
250 mm
H (min.)
a in mm
in mm
170
580
230
760
230
850
230
850
Height (H) for
Axis –Centre
the boiler guide
distance (AA)
in mm
in mm
680
225
860
340
1005
450
1005
450