Installation - Toshiba MMW-AP0271LQ-E Manuel D'installation

Masquer les pouces Voir aussi pour MMW-AP0271LQ-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 7
 Installation atmosphere
Installation atmosphere of the unit is as follows. Be careful of installation atmosphere.
It becomes a cause of failure of a product by dewing or freezing.
Installation atmosphere
90
85
80
70
60
50
40
30
20
10
0
0
5
 Installation space
Reserve sufficient space required for installation or service work.
Front side
200 or more
97-EN
Dry-bulb temp. (°C)
5 to 32
Wet-bulb temp. (°C)
24 (Max.)
RH (%)
30 to 85
Allowable dew point
23 or less
(°C Wet-bulb temp)
Permissible range
10
15
20
25
30
32
35
Dry bulb temperature (°C)
50 or more
500 or more
Front side
– 49 –
5

Installation

CAUTION
Strictly comply with the following rules to prevent damage of the hot
water modules and human injury.
• Do not put a heavy article on the hot water module or let a person get
on it. (Even units are packaged)
• Carry in the hot water module as it is packaged if possible. If carrying
in the hot water module unpacked by necessity, use buffering cloth or
other material to not damage the unit.
• To move the hot water module, hold the bottom face of the unit only.
Do not apply force to the other parts (refrigerant pipe, drain pan, water
pipe, foamed parts, resin parts or other parts).
• Carry the package by two or more persons, and do not bundle it with
plastic band at positions other than specified.
• To protect yourself from injury, always use PPE (Personal Protective
Equipment), that is, wear gloves.
• Install the Hot water module in a place strong enough to withstand the
following weights:
Hot water module weight with no water 17.8 kg (027) 20.3 kg (056)
Hot water module weight with full water 18.4 kg (027) 21.6 kg (056)
(Unit: mm)
98-EN