Selection Of Installation Place - Toshiba MMW-AP0271LQ-E Manuel D'installation

Masquer les pouces Voir aussi pour MMW-AP0271LQ-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 7
4

Selection of installation place

Avoid installing in the following places
Select a location for the indoor unit where the cool or warm air will circulate evenly.
Avoid installation in the following kinds of locations.
• Saline area (coastal area)
• Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or
pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the
unit).
Doing so may cause the heat exchanger and other parts to become corroded.
• Locations with atmospheres with mist of cutting oil or other types of machine oil.
Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat
exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such
problems to result.
• Locations where vapors from food oils are formed (such as kitchens where food oils are used).
The plastic parts to be damaged, and other such problems to result.
• Locations where an in-house power generator is used for the power supply.
The power line frequency and voltage may fluctuate, and the hot water module may not work properly as a result.
• On truck cranes, ships or other moving conveyances.
• The hot water module must not be used for special applications (such as for storing food, plants, precision
instruments or art works).
(The quality of the items stored may be degraded.)
• Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical
equipment or communication equipment).
(Malfunctioning or control trouble in the hot water module or noise may adversely affect the equipment's
operation.)
• Locations where there is anything under the unit installed that would be compromised by wetness.
(If the drain has become blocked or when the humidity is over 85%, condensation from the hot water module will
drip, possibly causing damage to anything underneath.)
• In the case of the wireless type of system, rooms with the inverter type of fluorescent lighting or locations
exposed to direct sunlight.
(The signals from the wireless remote controller may not be sensed.)
• Locations where organic solvents are being used.
• The hot water module cannot be used for liquefied carbonic acid cooling or in chemical plants.
• Location near doors or windows where the hot water module may come into contact with high-temperature, high-
humidity outdoor air.
(Condensation may occur as a result.)
• Locations where special sprays are used frequently.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior
of the hot water module, it may spontaneously combust and start a fire.
• Locations such as living rooms and bedrooms where you can easily be bothered by noise. Noise may become
a problem.
95-EN
CAUTION
• Do not install hot water module in a place where water freezes.
• Do not install the hot water module in a place where combustible gas
may leak.
• Do not install the hot water module in a place exposed to rain or
water.
• Do not install the hot water module near equipment which generates
heat.
• Do not install the hot water module to a movable object.
• Do not install the hot water module in a place exposed to vibration.
• The hot water module must be installed in accordance with national
wiring regulation.
• The hot water module must not be installed in a high humidity
condition area.
• The hot water module must not be installed in a high dusty area.
– 48 –
96-EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mmw-ap0561lq-e

Table des Matières