3.2 System able to be combined for MiNi-SMMS-e series (MCY-***)
The Mid temperature Hot Water Module is connectable to MiNi-SMMS-e.
M-HWM: Mid temperature Hot Water Module
No.
1
System capacity
2
Indoor connection capacity
3
M-HWM connection capacity per refrigerant system
Height between outdoor and indoor units (including M-HWM)
H1
4
Height difference
Height between indoor units
(including M-HWM)
H2, H3, H4
(*1): For more information, please read the Installation Manual provided with the outdoor unit. (Total capacity code of connectable indoor units)
(*2): For more information, please read the Installation Manual provided with the outdoor unit. (Where H1 is indicated)
(*3): Please read the Installation Manual provided with the outdoor unit. (Where H2 is indicated)
▼
Capacity code of outdoor unit, Maximum indoor unit quantity and total capacity code of indoor unit
MiNi-SMMS-e
of outdoor unit (HP)
MCY-MHP0806HS8*
MCY-MHP1006HS8*
▼
Capacity code of Mid temperature Hot water module
The capacity code of the Hot water module is different from the capacity code of the standard indoor unit.
Mid temperature Hot water module
Capacity rank type
Capacity code
Equivalent to HP
Equivalent to capacity
▼
Capacity code of standard indoor unit
Capacity rank type
Capacity code
Equivalent to HP
Equivalent to capacity
Capacity rank type
Capacity code
Equivalent to HP
Equivalent to capacity
89-EN
Item
Upper outdoor units
Lower outdoor units
Upper outdoor units
Indoor - Indoor
H2
Lower outdoor units
Upper outdoor units
Indoor - M-HWM
H4
Lower outdoor units
Upper outdoor units
M-HWM - M-HWM
H3
Lower outdoor units
Capacity code
Maximum indoor
unit quantity
8
12
10
16
MMW-AP0271LQ-E
MMW-AP0561LQ-E
027
(HP)
2.5
(kW)
7.1
005
007
009
012
015
018
(HP)
0.6
0.8
1
1.25
1.7
(kW)
1.7
2.2
2.8
3.6
4.5
5.6
030
036
048
056
(HP)
3.2
4
5
6
(kW)
9.0
11.2
14.0
16.0
– 45 –
M-HWM connection
Depending on the outdoor unit to be connected
130% (*1)
(Excluding M-HWM)
Max.
200%
(Including M-HWM)
80% (*1)
Min.
(Excluding M-HWM)
Max.
100% or less
(*2)
(*2)
10m
10m
See Figure 1
10m
10m
10m
10m
Total capacity code of indoor units (HP)
Standard indoor unit + M-HWM
Total capacity 80 - 200%
6.4 to 16.0
8.0 to 20.0
056
5
14.0
024
027
2
2.5
3
7.1
8.0
Without M-HWM connection
130% (*1)
80% (*1)
-
(*2)
(*2)
(*3)
-
-
-
-
90-EN