Configuration - JUMO iTRON 04 B Notice De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Configuration

H
Time-out
If no key is pressed for 30 seconds, the controller will automatically return to the temperature
display.
Parameters Individual parameters will not be visible if they have been disabled in the parameter ring
through the setup program (accessory).
h
Change over to the parameter level using
Process value input
Parameter Meaning
SEn
Transducer
connected transducer
uni
Unit
for the indicated temperature and parameters with temperature unit
OFF
Process value correction
temperature offset in °C or °F
dF
Filter time constant
to adapt the digital input filter (
At a signal step, 63% of the signal change has been registered
after the set time has elapsed.
If the filter time constant is large:
- high damping of interference signals
- slow reaction of the process value display to changes in process value
+
(hold both down for 5 seconds!)
dF
=0.0 switches the filter off).
Value range
from ... factory-set ... to
001 (Pt100)
040 (thermocouple J)
042 (thermocouple L)
043 (thermocouple K)
°C or °F
-99 ... 0 ... +999
0.0 ... 1.0 ... 99.9s
11