3.2. Technical data
Product application
Supply voltage
Power consumption
Power output relay
(heating cable)
Power supply terminals
Heating cable terminals
Alarm terminals
Sensor terminal - Pipe
Alarm relay
Settings
Operating temperature
Selectable temperature
Material
Dimensions
Ingress protection class
Weight
Mounting
Entries
Storage temperature
Flammability class
Temperature sensor type
Sensor tip dimensions
Sensor cable length
Temperature range
nVent RAYCHEM Pipe freeze protection heating
cables only
Electrical properties
180-253 VAC; 50/60Hz
5,3 W max
25 A / 230 VAC
3 x 6 mm² max
3 x 6 mm² max
3 x 1,5 mm² max
2 x 1,5 mm² max
Single pole double throw relay, volt-free; Max.
switching capacity (resistive load only)
1 A/30 VDC 0.5 A/125 VAC, Max.: 60 VDC/125
VAC
All settings are stored in non-volatile memory
–40°C to +40°C ambient
0° C to +85°C
Enclosure
Polycarbonate
210 mm x 90 mm x 85 mm
IP 65
990 g
DIN-Rail mountable 35 mm
2 x M25 and 2 x M20
–40°C to +50°C
D category (DIN EN 60730/VDE 0631-1)
Sensor
Standard NTC 2,0 kOhm at 25°C, 2 wires
Ø 5 mm; length 20 mm
5 m; extendable up to 150 m , 2 x1,5 mm²
–40°C to +90°C