1.1 Designated Use
• Hot water heating boiler.
• Indoor installation.
• Closet or alcove installation.
• Catagory I or III Venting.
• Direct vent boiler.
• For use with natural gas or liquefied petroleum gases
(LP/propane).
• Directly heat potable water. Indirect heating is
acceptable.
1.2 The unit MUST NOT:
• Heat water with non-hydronic heating system chemicals
present (example, swimming pool water).
• Exceed 185°F (85°C) system design temperature.
• Exceed MWAP 43.5 PSIG
1.3 Operational Features
• Modulating: 3-1 turn down.
• Integral Dual Limit.