Télécharger Imprimer la page

SERVODAN 41-351 Notice D'utilisation page 9

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Technical data
Input:
Supply voltage ......................................230 V AC 50 Hz +/- 10%
Power consumption (standby)..............0.2 W (without light fi ttings).
øL
........................................................L
1
øN .........................................................N
Pushbutton:
øL
........................................................
1
ø
........................................................
Output:
Relay .....................................................NO, 230 V, µ 10 A
Load:
Fluorescent tubes, not compensated ..1200 VA
Max. compensation capacity ..............140 µF
Max. starting peak ...............................165 A/20 m sec.
Performance:
Output signal ........................................1-10 V/max. 10 mA
Time range ...........................................1–60 mins
Lux range ..............................................50 – 1500 lux
Orientation lighting level .......................5–100%
Orientation lighting Time ......................0–60 mins, infi nite
Enclosure class ....................................IP 20
Insulation class .....................................CL. I
Ambient temp. ......................................-5°C to +50°C
Approval:
CE in accordance with .........................EN 60669-2-1
Accessories
IR Remote .............................................Model 41-922
IR User Remote ....................................Model 77-921
Settings
Factory settings:
Application ................................App. Man
Setpoint .....................................300 lux
Setpoint hysteresis ....................20%
Orientation lighting level ............5%
Orientation lighting time ............1 min.
Off delay (Time) .........................10 mins
Setting of Lux and Time ............Via IR Remote
LED indicators:
Red LED fl ashes when activity is detected by the presence detector.
Green LED fl ashes when the pushbutton power switch or the IR
Remote is activated.
If the buttons on the IR-remote are pressed, the sensor is
unlocked and there is no indication from the Green LED, then the
sensors is in min. or max. of the settings.
Blue LED is lit when test mode is selected.
Blue LED fl ashes when setting the setpoint, indicating over-
illumination.
Manual dimming using the pushbutton:
When the dim function has been activated, the lighting must be
switched off so that it can be switched on, and thus function with
daylight control (according to built-in light sensor).
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Function App. Man
Manual, Factory settings
Function description:
Ceiling lighting
Daylight control is switched on and off via the pushbutton.
The light can be switched on when light is needed according to
the preset parameter.
As long as the presence detector registers activity, the lighting
will be adjusted according to the preset parameters.
As daylight increases, lighting in the room starts to dim until the
preset minimum light level is achieved.
If there is suffi cient incident daylight, the lighting is dimmed
to minimum and after 60 sec. it switches off (Cut-off function,
supply to HF-ballasts is switch off).
The light switches off automatically after a preset period, when
the presence detector does not register activity within the
detection area.
Dimming of lighting
A long press of the pushbutton enables the lighting to be
adjusted up/down.
Manual override using IR Remote.
Function App. Auto
You must use an IR Remote (accessory) to select App. Auto.
Function description:
Ceiling lighting
When a presence detector registers activity and light is required,
the lighting comes on automatically.
As long as the presence detector registers activity, the lighting
will be daylight-controlled according to the preset parameters.
As daylight increases, lighting in the room starts to dim until the
preset minimum light level is achieved.
If there is suffi cient incident daylight, the lighting is dimmed
to minimum and after 60 sec. it switches off (Cut-off function,
supply to HF-ballasts is switch off).
The light switches off automatically after a preset period, when
the presence detector does not register activity within the
detection area.
Manual switching off of lighting
If a pushbutton is used, a short press will switch off the light.
After a blackout period of approx. 10 secs the PIR is ready again
for auto switch on.
Dimming of lighting
A long press of the pushbutton enables the lighting to be
adjusted up/down.
Manual override using IR Remote.
41Y351_03_R2_110427KOE
41Y351_03_R2_110427KOE
GB
9(22)

Publicité

loading