65-411
7. TECHNICAL DATA
- Supply voltage 230V ±10%, frequency 50Hz
- Installation: DIN-rail (6U)
- Weight: ± 440g
- Allowed ambient temperature: see load table
- Designed for use in an environment with non-condensing atmospheric humidity
- Own consumption: ±2,5W
- Maximum temperature of cover (tc): 90°C
- Maximum wire diameter per terminal
- power supply and load: 2 x 2,5mm
- input: 2 x 2,5mm
- Minimum load: 100W
- Maximum load: 1400VA resistive, inductive and capacitive (t<35°C)
- Maximum voltage drop across dimmer: -5%
- Protections:
- electric thermal protection (105°C) with automatic restart (Light is reduced
- single thermal overload protection (135°C)
- Complies with standards EN60669-2-1 and EN55015
- Maximum distance to last push button: - in case of simple button control: 100m
- Max. output voltage: supply voltage x 0,95 (dissipated power = ± 1% of the absorbed power
= ± 14W)
49
2
or 1 x 4mm
2
2
to minimum. It the temperature does not drop, the load is switched off).
or 1 x 4mm
2
- in case of DALI control: see DALI specifications
ε
R,L,C
EN