Question: How are the outputs (relays) protected, or are internal fuses fitted upstream of the relays?
6
Answer: The connecting cables for supplying power to the outputs (L0-L3) must be protected with a 10 A automatic circuit breaker.
Make sure the loads and the power consumption (230 V~ /50 Hz /1A) are evenly distributed!
Question: How high a load can the 24V sensor connection withstand?
7
Answer: Max. 100 mA.
Question: Can direct current motors be used as well?
8
Answer: No, only alternating current motors (230V~/50Hz max. 1A).
Question: Can motors be connected in parallel?
9
Answer: No, only one motor (230V~/50Hz max. 1A) per output.
Question: Is the Compact system compatible with the PHC system?
10
Answer: No!
Question: Can several buttons be connected to one input in parallel?
11
Answer: Yes, several buttons can be connected in parallel.
Question: How high a load can the outputs withstand?
12
Answer: At 230 V~ /50 Hz max. 1A per output.