Installation Guide
Actuator Electrical Settings ⓭
Prior to commissioning, the settings for the
input und output signals and for the final
positions must be carried out.
Prior to any settings, dismount the
cover
.
Switch Designations
Pushbutton S1
Switch S2
Switches 5, 6 ④
Switch 5 must be on "OFF".
Switch 6 has no function.
Setting the Output Signal
The output signal is proportional to the
actuating stroke.
Setting of the switch S2, see
Setting the Input Signal
Connecting the lines to the terminal strip
determines the "current" or "voltage"
input signal, see "Electrical Connection
Diagram", ⓫.
Setting of 0 or 4 mA, 0 or 2 V, see
Setting the Final Positions
When the stroke is set (see ⓯), the
final positions "Valve OPEN" and "Valve
CLOSED" must be equalized with current
and voltage values 0(4) - 20 mA, 0(2) - 10 V.
Valves VFG.., AFQM 6
Setting the final position "Valve
CLOSED"
• Set switches 1 and 2
• Press pushbutton
until the valve
is completely closed and the direction
indicator
stops.
• Press pushbutton
.
The final position "Valve CLOSED" is set.
Setting the final position "Valve
OPEN" ⓱
• Set switches 1 and 2
• Press pushbutton
until the valve
is completely open and the direction
indicator
stops.
• Press pushbutton
.
The final position "Valve OPEN" is set.
• Set switch 1 to standard mode
• Unscrew the stroke limiting screw
one turn.
The setting of the final positions for the
valves VFG.., AFQM 6 is completed.
6
DEN-SMT/SI
AME 410, AME 413
• Set the assignment of the effective
direction for the input and output
signals, see ⓴
Setting the Final Positions for
valves VFU 2
In contrary to the valves VFG .., AFQM6, the
valve VFU 2 ⓲
direction.
The valve VFU 2 is opened by the safety
return function.
Setting the final position "Valve
OPEN" (VFU 2) ⓲
• Set switches 1 and 2
• Press pushbutton
is completely open and the direction
indicator
⓮①
.
• Press pushbutton
The final position "Valve OPEN" (VFU 2)
is set.
Setting the final position "Valve
CLOSED" (VFU 2) ⓳
• Set switches 1 and 2
⓮②
.
• Press pushbutton
is completely closed and the direction
indicator
• Press pushbutton
The final position "Valve OPEN" is set.
• Set switch 1
The setting of the final positions for the
valves VFU 2 is completed.
• Set the assignment of the effective
direction for the input and output
signals, see ⓴
.
Assignment of the effective
direction for the input and output
signals
Setting of switch 2 ⓴
Then, remount cap nut and cover.
Dismounting of Valve and
Actuator
.
Danger
Danger of injury by steam or hot water!
Valve without actuator is open
.
is in the actuator.
by
It is absolutely necessary to depressurize
system prior to dismounting.
Carry out dismounting in reverse order as
mounting.
has a reversed closing
.
until the valve
stops.
.
until the valve
stops.
.
21
, sealing
VI.AA.R4.6Z