TEST AND MAINTENANCE PLAN

The following must be checked:
Interval
1/2 annual
Test run up to maximum nominal speed and then deac-
tivate again.
1/2 annual
Check fan and drive motor for running noises.
Annual
Test run for at least 20 minutes and then deactivate
again.
For fans with bearing condition diagnostics, operate fan
until steady-state is reached (around 60-75 minutes)
before reading out values (see Installation and Operating
Instructions for LZD).
Annual
General visual inspection and check of fan condition for
external soiling, correct fastening, corrosion and dama-
ge.
Clean components for functional integrity if needed.
Annual
Check flat roof base and on-site substructure/foundation
for damage and corrosion as well as correct
fastening.
Annual
Check flexible connectors and connections for tension-
free installation, tightness, correct fastening, soiling
and damage.
Clean components for functional integrity if needed.
Annual
Check air gap between inlet nozzle and radial impeller.
Annual
Check drive motor for soiling, corrosion, damage and
correct fastening. Clean components for functional integ-
rity if needed.
Annual
Check impeller for soiling, corrosion, damage and correct
fastening.
Clean components for functional integrity if needed.
Annual
Check inspection opening for tight fit, corrosion and
damage.
Annual
Check protection devices (protection grilles, etc.) for soi-
ling, corrosion, damage and correct fastening.
Clean components for functional integrity if needed.
Annual
Check discharge grille and immediate environment for
unhindered air outlet, and remove any dirt.
Annual
Check accessory components (deflector, hood attenua-
tor, backdraught shutters, extension ducts, etc.) for soi-
ling, corrosion, damage and correct fastening.
Clean components for functional integrity if needed.
Check isolator and connection cable for correct position,
Annual
damage and corrosion.
Annual
Check intake duct for unhindered cooling air intake and
remove any dirt in the cross-section.
Annual
Check motor protection device, for ventilation mode
(motor protection device, not in case of fire).
Annual
Check on-site bridging of frequency converter and motor
protection devices in case of fire.
Smoke exhaust roof fans F400/F600 – B VD
Test and maintenance work
Fan B VD F400/F600
Standard
incl . LZD
Basic
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
22
To be carried out by
incl . LZD
Comfort
x
Instructed personnel
x
Instructed personnel
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist
x
Specialist electrician
x
Specialist
x
Specialist
x
Specialist