Setup and operating options
General setup diagram
CODE
DESCRIPTION
P0
Obstacle detection sensitivity
P1
Closure approach speed
P2
Total operating mode
P3
Partial operating mode
P4
Safety input
10
VALUES
0 = low sensitivity
1 = low sensitivity
2 = Standard
3 = high sensitivity
0 = no slowdown
1 = short soft stopt
2 = long soft stop
0 = sequential
1 = sequential + timed close
2 = automatic closure
3 = automatic closure by cells
0 = sequential
1 = sequential + timed close
0 = no safety mechanism
1 = safety mechanism with self test
2 = safety mechanism without self test
COMMENTS
If this parameter is modified, the installer must check that the limitation of forces
complies with appendix A of the standard EN 12 453.
P1=0 the door does not slow before closure.
P1=1 the door speed slows 20 centimetres before closure
P1=2 the door speed slows 50 centimetres before closure
If this parameter is modified, the installer must check that the limitation of forces
complies with appendix A of the standard EN 12 453.
Chaque appui sur une touche de la télécommande provoque le mouvement
du moteur (position initiale : porte fermée) selon le cycle suivant :
ouverture, stop, fermeture, stop, ouverture, ...
In sequential mode with automatic timed close:
- the door is closed automatically after the timed
delay programmed in parameter t0.
- pressing a button on the remote control interrupts
the movement taking place and the timed close.
In automatic closure mode:
- the door is closed automatically after the timed
delay programmed in parameter t0.
- pressing a button on the remote control during
Automatic closure mode
opening has no effect.
operation is only possible if
- pressing a button on the remote control during
photoelectric cells are fitted,
closing causes it to reopen.
i.e. P4=1 or P4=2.
- pressing a button on the remote control during the
timed close restarts the timed delay.
- After the door is opened, movement in front of the
cells (safe closure) will close the door after a short
timed delay (fixed at 5 seconds).
- If there is no movement in front of the cells, the
door will close automatically after the timed close
programmed in parameter t0.
- If there is an obstacle in the cells' detection zone,
the door will not close. It will close once the
obstacle is removed.
Each press on the remote control causes the motor to move (initial position: door
closed) as per the following cycle: open, stop, close, stop, open...
Automatic closure mode operation is only possible if photoelectric cells are
fitted, i.e. P4=1 or P4=2.
In sequential mode with automatic timed close:
- the door is closed automatically after the timed delay programmed in
parameter t2,
- pressing a button on the remote control interrupts the movement taking place
and the timed close.
If value 0 is selected, the safety input is not taken into account.
If value 1 is selected, the system's self test is run at the start of every operating cycle.
If value 2 is selected, the safety system runs without a self test: it is essential
to test its proper operation every six months.