been set with the Turning Knob 23, the inverter switches on at once. The transfer is
carried out in 0.02 seconds. This quick transfer ensures a break-free function for
most appliances. If you have an alternating voltage back at the input AC IN, transfer
system starts up again with-out any break, and the inverter is stopped.
4.7.3 Delayed mode of the Transfer System
The delayed mode of the transfer system „Transfer Delay ON" is programmed with
the slide switch on front with the cable connections. The HP-COMPACT provides a
break-free alternating voltage for the appliance. A quick transfer switch is not always
sensitive nor is it always desired. For example, when the appliances are operated by
a small back-up generator. An overload of a short period on such a generator, i.e.
start of a vacuum cleaner etc., has the effect of decreasing the voltage for a short
time. As in such cases the transfer to the Inverter is not desired, the transfer system
can be programmed with a delay. When the slide switch (Transfer delay) is in the
„On" position, the transfer to the inverter takes place with a delay of 5 seconds. If the
voltage falls below 100Vac, the transfer takes place without delay ! The transfer
switching to the Inverter takes place without any break.
4.8

The Multifunctional Contact

In the HP-COMPACT there is a built-in programmable power relay. The potential-free
change-over contact (NO – NC) of this power relay is connected to the screw
terminal AUX CONTACT.
Maximum Contact load: 230Vac / 12Vdc / 24Vdc / 16A !
With the Push Button 21 „AUXILIARY CONTACT" the contact can be manually
switched on or off independently from programming and from the operating situation.
The LED 5 "Contact active" shows the status of the contact. The drawing up the
screw terminal "AUX CONTACT" is the inactive position mode, LED 5 "Contact
active" off.
The switching on and off of this contact can be freely programmed for every
operating situation of the HP-COMPACT witch situation is indicated with a LED.
There is no limitation to its application and it is left to your wishes as to where and
how you would like to use it. The example and the setting of this contact are
explained in chapter 5.4.
In factory we program this for a dysfunction alarm. The contact is active when one of
these situations is detected:
 Over temperature (LED 10 lit)
 Overload (LED 11 lit)
 Over or less voltage of batteries (LED 12 lit or blinking)
 HP-COMPACT is turned off manually or with a fault (LED 13 lit)
In case this function is not wished, it must be modified by programming according to
procedure in chap. 5.4.
> 36Vdc / 3A !