Auxiliary Contact - Studer Innotec HP-COMPACT-HPC 2800-12 Manuel D'utilisation Et De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

STUDER Innotec
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change
status) for minimum 2 seconds simultaneously.
With the Push Button 20 (select) select which of the battery level and of the
absorption time have to be changed.
These four red LED's show the function set:
Low voltage
Float charge
Absorption (End of charge)
Equalization
Absorption Time
With the Push Button 19 (Change status) set the desired parameter (voltage or time)
to modify (LED 14/ 15/16/17/18). Push Button 19 (Change status) to set the desired
value according to the table 5.3.2.
If desired, repeat the operation with any
other parameter (voltage or time) to be
changed.
If during 30 seconds no buttons are
pressed,
the
selected
automatically
stored
COMPACT switches back in to the
normal operating status.
The voltage levels and times changed
through programming are only first
active with the next charge cycle!
The voltage level which is not suitable can greatly reduce the battery life or
could even destroy it ! Therefore check beforehand with your battery supplier.
5.3.2 Table of voltage and timing threshold
The voltage levels (low voltage, float charge, end of charge and equalization) and the
du-ration of the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance
with the diagram shown below:
Low voltage
LED 13
12
24
48
12
14 12.0 24.0 48.0 13.7
15 11.8 23.6 47.2 13.6
16 11.6 23.2 46.4 13.5
17 11.4 22.8 45.6 13.4
18 11.2 22.4 44.8 13.3
The heavy printed values show the standard settings.
5.4

Auxiliary contact

5.4.1 Principle
The Auxiliary Contact can be basically programmed for any operating situation of the
HP-COMPACT which is indicated with a LED. The programming is possible for one
or more operating situations. If the contact is programmed for many situations, it is
activated as soon as the HP-COMPACT finds itself in any one of the programmed
LED 13 (ON/OFF)
LED 12 (Batt. Low/high)
LED 11 (Overload)
LED 10 (Overtemp.)
LED 10/11/12/13 (altogether)
values
are
and
the
HP-
Float charge
Absorption
LED 12
LED 11
24
48
12
27.4
54.8
16.2
32.4
27.2
54.4
15.6
31.2
27.0
54.0
15
26.8
53.6
14.4
28.8
26.6
53.2
14.2
28.4
HP-COMPACT V5.7
Equalization
LED 10
24
48
12
24
64.8
16.2
32.4
62.4
15.9
31.8
30
60
15.6
31.2
57.6
15.3
30.6
56.8
15
30
HP-COMPACT
Absorption
Equali-zation
time
LED
LED 10/11
10/11/12/13
48
12/24/48
12/24/48
64.8
4h
63.6
3h
62.4
2h
61.2
1h
60
0 – 1'
time
3h
2h
1h
40'
20'
24/80

Publicité

Table des Matières
loading

Table des Matières