The Caramatic DriveTwo can also be operated with only one gas cylinder.
The non-return gas valve prevents gas from escaping from the free connection.
When operating with only one gas cylinder, the free connection must be connected to the
Caramatic DriveTwo can be closed by means of the sealing nut
withdrawal direction on the rotary knob in the direction GREEN of the connected cylinder.
If LPG is withdrawn too quickly or is continuously withdrawn from the cylinder on the operating
side, the temperature of the gas falls and, as a result, the cylinder pressure drops below the
required inlet pressure of the regulator. LPG is then also withdrawn from the spare cylinder.
Proper operation of the system is no longer guaranteed.
The LPG cylinders on both sides may be emptied simultaneously or also at different rates.
The gaskets at the inlet connections (if provided) must be replaced when re-assembling!
Make sure that the gaskets sit properly in the mounting and that the screws are tightened.
The LPG cylinders must be upright when gas is being withdrawn.
Gas is withdrawn only from the gaseous phase.
The gas cylinders must be secured so that it cannot topple over.
Protect gas cylinders against radiant heat or heat from heating appliances.
Observe the installation regulations in the respective countries.
TROUBLESHOOTING
Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
No gas flow.
Abnormal flame pattern of
non-adjustable pressure
regulator
In case of continuous gas escaping via the pressure relief valve PRV via the breather the
pressure regulator must be replaced with a new pressure regulator.
In case of gas smells, leaks, gas escaping via the PRV or faults in the consumption
equipment, SHUT DOWN THE SYSTEM immediately. Contact a specialised company.
RESTORATION
If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is
no dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.
26 / 44
Action
Close the gas supply.
Do not use any electric switches.
Do not use a phone in the building.
Ventilate rooms well.
Shut down the LPG system.
Contact a specialised company.
Open the gas cylinder valve, shut-off fittings or excess
flow device.
Pressure regulator is defective, replace.
Activation of the crash sensor see START-UP.
Compare the nominal outlet pressure with the nominal
connection pressure:
if they do not correspond, replace the pressure regulator
or the gas appliance.