GAS TRAIN ASSEMBLY DIAGRAM
N° BT 8806
FASTENING THE BURNER TO THE BOILER
The burner must be applied to the boiler's iron plate, where the stud bolts given as standard accessories have
already been fitted in accordance with the plate drilling.
It is advisable to electrically weld the stud bolts to the internal part of the plate to avoid extracting them together
with the unit's locking nuts, should the burner disassembled.
To fit the insulating flange between the burner and the boiler plate, remove the end section of the combustion head.
The relative nuts and washers required for connecting the burner to the boiler have been supplied as standard
accessories. The unit is equipped with a cylindrical combustion head; it is advisable to fasten the boiler's iron
plate first and then the burner. When the boiler door is not fitted with heat insulation, it is necessary to insert an
insulating protection at least 10 mm. thick between the plate and the boiler.
The boiler plate should be according to our drawing and have a minimum thickness of 10 mm. in order to avoid
possible deformation. Before fastening the burner to the boiler, put the sliding flange in the position conside-
red necessary to allow the burner head to penetrate the combustion chamber as far as required by the boiler
manufacturer. When this operation has been completed, connect the burner to the gas pipeline according to the
instructions contained in the following pages.
39 /
000608006_2007/06