MAINTENANCE
Skilled staff has to perform yearly the following operations:
- Check the valve inside tightness.
- Filter cleaning.
- Fan and head cleaning.
- Check the position of the ignition electrode tips as well as the control electrode.
- Calibrate the air and gas pressure switches.
- Check the combustion by means of CO
- Check all the gaskets and seal tightness.
EM 16/M-E
To gain access to the main compo-
nents, remove the cover, as shown in
(Fig.1). Combustion head maintenance
should be made as follows:
- Close the gas cock and disconnect
the gas train. Unscrew the screws 1
and remove the cover 2 (fig.1).
- Unscrew the screws 3 and the central
pin 4 (fig.2).
- Hang the component holder plate
into the service position 5 and effect
combustion head maintenance (fig.3)
UK
-CO-FUMES TEMPERATURE bearings.
2
48
M
fig. 1
fig. 2
fig. 3