CALIBRATION AND SETTING UP
1 Ratio V
2 Ratio N
3 PL Air pressure check point
- Start the burner at the maximum flow-rate.
in the fumes, adjusting the GAS-AIR ratio V via screw 1.
- Measure the CO
2
- Check the counter to see whwthwr the flw-rate is as required: to adjust the quantity of gas
act on the air gate servo control with small movements of the red cam until you obtain the
desired flow-rate.
- Once you have obtained the desired flow-rate repeat the combustion test and, if necessary
fine-tune the GAS-AIR ratio V by acting on screw 1.
- Bring the burner to the 1st stage position or minimum flow-rate (by adjusting the orange
cam) and check combustion by acting on N via screw 2.
- Re-check combustion at maximum flow-rate and various intermediate flow-rates as the
burner is designed for continuos modulation.
MB VEF 407/412
4 PBr Gas pressure check point
5 PF Combustion chamber pressure
check point
43
UK