Equipment - Lamborghini Caloreclima EM 16/M-E Notice D'installation Et D'entretien

Bruleurs a gaz modulants
Masquer les pouces Voir aussi pour EM 16/M-E:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EQUIPMENT

LME EQUIPMENT
The release pushbutton on the equipment is the main component for accessing all the dia-
gnostic functions (activation and deactivation) as well as for releasing the control and che-
cking device. The release pushbutton has a multicoloured led which indicates the state of the
control and checking device during operation and when the diagnostic function is in use.
EQUIPMENT STATE INDICATORS
Condition
Standby, other intermediate states
Ignition stage
Correct operation
Incorrect operation, current level of flame detector below permitted
minimum
Drop in voltage
Burner lock out
Fault (see table)
Stray light before burner ignition
Rapid flashing for diagnostics
If the burner is locked out, there will be a steady red light on the lock out pushbutton.
By pressing the transparent pushbutton, the control and checking device will be released.
By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes
rapidly). The table below describes the causes of the lock out or fault in relation to the num-
ber of flashes (always red). The diagnosis function is interrupted by pressing the release
button for at least 3 seconds.
DIAGNOSIS OF LME EQUIPMENT FAULTS AND LOCK OUT
Visual indication
2 flashes
3 flashes
4 flashes
5 flashes
6 flashes
7 flashes
8 flashes
9 flashes
10 flashes
14 flashes
No flame signal
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
- No ignition
- Air pressure switch failure
- Air pressure switch loss of signal after T10
- Air pressure switch contact open
Stray light on ignition
Time out "LP". "LP" is welded in working position
Free
No flame signal during operation
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
Free
Free
Incorrect electrical connection or damage to equipment
Open thermostats switch line
41
Colour sequence
Yellow flashing
Green flashing
Alternating yellow red
Red flashing
Alternating green red
Red rapid flashing
Possible causes
M
No light
Green
Red
UK

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Em 26/m-e

Table des Matières