Ventilation Requirements - Fisher & Paykel DCS CPU/CPV-484GG Guide D'installation

Masquer les pouces Voir aussi pour DCS CPU/CPV-484GG:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

VENTILATION REQUIREMENTS

A suitable exhaust hood must be installed above the cooktop. The following chart indicates the minimum
blower capacity recommended for hood ventilation.
VENTILATION
UNIT
HOOD
BLOWER
* Cooktops featuring a grill require a 1200 CFM ventilation unit.
CAUTION:
Ventilation hoods and blowers are designed for use with single wall ducting. However, some local building codes
or inspectors may require double wall ducting and/or damper. Consult local building codes and/or local agencies,
before starting, to ensure that hood and duct installation will meet local requirements.
Hood blower speeds should be variable to reduce noise and loss of heated or air conditioned household air
when maximum ventilation is not required. Normally, the maximum blower speed is only required when using
the grill.
For best smoke elimination, the lower edge of the hood should be installed a minimum of 30" to a maximum of
36" above the cooktop cooking surface, see section 'Cabinet preparation'. If the hood contains any combustible
materials (i.e. a wood covering) it must be a minimum of 36" above the cooking surface.
Due to a high volume of ventilation air, a source of make-up air (outside replacement air) is recommended. This
is particularly important for tightly sealed and insulated homes. A reputable heating and ventilating contractor
should be consulted.
STANDARD COUNTER
INSTALLATION
RECOMMENDATONS
23" Deep x Unit Width
48" Cooktop
1200 CFM
*36" Cooktop
600-1200 CFM
ISLAND INSTALLATION
RECOMMENDATONS
30" Deep x 36" at Bottom
1200 CFM
600-1200 CFM
11
US
CA

Publicité

Chapitres

Table des Matières
loading

Table des Matières