The specified minimum
height must be observed
exactly
Fig. G1:
Installation variant A:
duct lengths of up to
35 cm
the minimum
height for installation of
the exhaust cowl is 20 cm.
Installation variant B:
duct lengths of up to
75 cm
mini-
mum height of 33 cm.
Installation variant C:
duct lengths of up to
120 cm
mini-
mum height 66 cm
The double
support DSW must be in-
stalled.
1. Fig. G1:
2. Fig. G2:
upper
Always install a new
O-ring (5) after any disas-
sembly work!
lower
The flue gas pipe
with insulating duct
and combustion air pipe
must be rising over its
entire length
A water
trap may otherwise devel-
op, obstructing the free
passage of the exhaust
gases!
Fig. G3:
over
Always install a new
O-ring (5) after any disas-
sembly work!
Fig. G3:
upper
lower
Exhaust routing
via the roof
Only Truma stainless steel
flue gas pipe AE 3 may be
used with the Trumatic
S 2200
Total length of the
exhaust gas duct: max.
3 m!
Fig. F:
1. Fig. H1:
2. Fig. H2:
lower
lower
Always install a new
O-ring (5) after any disas-
sembly work!
Fig. H3:
1. Fig. H4:
1. Fig. H5:
upper
upper
upper
Always install a new
O-ring (5) after any disas-
sembly work!
4. Fig. H4:
The flue gas pipe
(40) with insulating
duct (41) must be ascend-
ing along its entire length
and securely and perma-
nently installed
since other-
wise a water pocket may
form that will prevent the
flue gas from exiting
freely.