UPS Functional Descriptions
3.
3-1 UPS Front Panel Display Descriptions
LCD panel
LCD Display
Green LED steadily lights up to indicate that the Utility input voltage is within the
window (80Vac~144Vac, or 160Vac~288Vac); the LED flashes flickeringly to indicate
that the Utility input voltage is within the acceptable window (60Vac~79Vac, or
120Vac~159Vac).
,
Green LED lights up to indicate there is an output available at the Programmable
Outlet 1 & Programmable Outlet 2.
Amber LED lights up to indicate the Bypass Input is normal.
UPS Fault LED
UPS On/Alarm Silence
UPS OFF Switch
Special functions log in/out
Go to next page
Go to previous page or change the setting of the UPS.
To re-confirm the change of UPS Setting
Manual Bypass: press "
3 seconds to transfer from "Inverter to Bypass" ( the bypass led continuously
"blink" and the buzzer will beep intermediately ) or "Bypass to Inverter", when the UPS
is on Line Mode and the Bypass Voltage Window is Normal.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 11 AA 68 203 03
ON-KEY" and "
Up-KEY" key simultaneously for approx.
32