Product Introduction
2.
2.1 General Characteristics
1. True online technology continuously supplies your critical device with a stable,
regulated, transient-free pure sine wave AC Power.
2. High Frequency Transformer-less technology with rack/tower convertible enclosure
enables the UPS for integration even in the most difficult of environment with
space constraints.
3. This UPS is equipped with fully digitalized control logic for greater functionality and
enhanced high level of power protection. Digital signal processing (DSP) also
provides the UPS with powerful communication capability, which enhances the
flexibility for easy remote control and monitoring
4. Wide input voltage tolerance from 60V ~ 144V (110V version) or 120V~288V
(220V
unnecessary battery drain and helps extend the battery life span.
5. DC-start function ensures the start-up of UPS even during power outages.
6. Revolutionary battery management circuit analyses battery discharging status to
adjust battery cut-off point and extend the batteries' life span.
7. Active Power Factor Correction (PFC) control function constantly maintains the UPS
Input Power Factor (PF) at > 0.99 for superb energy efficiency.
8. Selectable Bypass input voltage tolerance (Sensitivity low/high) to prevent under or
over voltage being supply to the loads at Bypass mode. The selectable Voltage
ranges are (i) Sensitivity Low: 90/180~130/260V & (ii) Sensitivity High:
97/194~130/260V.
9. Vast Selectable Output Voltages (100/110/115/120/127V or 200/208/220/230/240)
to meet various voltage systems.
10. The UPS is designed to comply with various stringent international standards for
Electromagnetic Interference & protection (EMC).
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
31
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 11 AA 68 203 03
version)
allows
under-voltage
or
over-voltage
correction
without