UPS Default Settings and Their Alternatives
1. Make sure the UPS is not "ON" yet, which means it is not in Line Mode or Backup
Mode. Press on "ON" Switch
approx. 3 seconds, the buzzer will sound twice, the LCD display screen shows as
drawing P1, then the UPS is under setting mode now.
2. To scroll down the LCD screen, you may refer to Chapter 4.4.1.3. Point 1.
3. Except Buzzer (as Drawing P1 & P2) and self-test (Q1 & Q2), all the rest default
settings may be changed by pressing scroll up
4. Drawing R1 and R2 mean the bypass input acceptable window, it can be 180Vac~
260Vac for 220Vac system, 90Vac~130Vac for 110Vac system or 194Vac~260Vac
for 220Vac system, 97Vac~130Vac for 110Vac system.
5. Drawing S means the bypass frequency window of the inverter output, the
acceptable setting values are +/-3Hz and +/-1Hz.
6. Drawing T means the acceptable Inverter Output Voltage, of which voltage is 200V,
208V, 220V, 230V, or 240V for 220Vac system, or 100V, 110V, 115V, 120V and
127V.
7. Drawing U1, U2 and U3 mean the operation modes of the UPS, of which alternative
is Online, fixed 50Hz Output or fixed 60Hz Output.
8. Drawing V means the adjustments of the Inverter Output, which may be calibrated
as 0%, +1%, -1%, +2%, -2%, +3%, or -3%。
9. When all the setting changes are done, press "Enter" key pad
changes when the LCD screen shows as drawing X. All those changes will be
activated only when the UPS is re-turned on. The LCD screen will be back to the
original screen before setting.
X
10. Turn off the UPS and the input breaker of the Utility.
11. Your Setting changes are complete.
UPS is Off Due to Unknown Reason and Its Trouble Shooting
1. If there is a serious abnormal condition occurred, the UPS will lock itself in "OFF"
position as shown in the drawing Y and a abnormal message will show in the LCD
screen.
Y
2. For some special conditions, the UPS will lock itself; however, it is still allowed to
have bypass output in most of conditions and the LCD screens will show as
drawing Z and error message will be shown on the screen.
Z