4-4 Operation
LCD panel
Start Up In Normal Mode
1. Make sure the voltage of Utility matches with the input voltage window of the UPS
and ensure the grounding is connected properly.
2. Connect the UPS to the wall Receptacle of the Utility. Turn on the main "ON"
switch to start up the UPS. LED
Bypass are normal. The LCD will illustrate from drawing A to drawing B.
A
B
3. Then, the UPS is on Stand-By Mode now and it will proceed self-test automatically.
If there is no abnormal message occurred, it means the pre-start-up of the UPS is
successful and the charger starts to charge the batteries.
4. Press the UPS On Switch '
If the UPS start-up is successful, the LCD display changes from drawing B to
drawing C
C
5. In case of failure in self-test, the LCD display will illustrate as drawing D, then, an
error code or error status will be shown on the screen.
D
E
6. Your start-up operation of the UPS is completely now as illustrated as drawing E.
Make sure the UPS is plugged onto the wall receptacle for charging at least 4 hours
and the batteries of the UPS are fully charged
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 11 AA 68 203 03
and
light up to indicate the Utility and the
'for approx. 3 seconds, then the Buzzer sounds twice.