3-3 Operating Modes & Voltage System Configurations
Download and open the "UPS Setting Tool" Software to see the screen as below
System Configuration Settings
1. System Voltage Selection:Select Input Voltage
110V or 220V
2. Voltage Configurations:Select UPS Output
Voltage 200V/208V/220V/230V/240V or
100V/110V/115V/120V/127V
3. UPS Modes:Select Normal/CF50*/CF60* Mode
4. Output Voltage Fine Tuning : Output Voltage
Regulation from 0~±3%
5. Bypass Voltage Windows:Sensitivity: Select
Sensitivity Low/Sensitivity High**
110V
220V
6. Syn-Frequency Window:Select 3Hz/1Hz Inverter Freq synchronizing range
7. Com Port:Select the Com Port of PC
8. Click on "Write" to confirm the configuration settings. The UPS will beep twice to
acknowledge setting is successful.
9. Turn off the UPS and unplug input power cord from AC Power Utility receptacle to
shut down whole unit without internal power supply existing, after setting is
complete. 3 seconds later reconnect input power cord into AC Power Utility
receptacle and turn on the UPS, referring to the section 4.4 Operation. The UPS will
perform in new settings.
Note:
*CF50/CF60 = Frequency Converter mode 50 to 60Hz or vice versa
**Sensitivity Low: 90/180~130/260V
Sensitivity High: 97/194~130/260V
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
35
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 11 AA 68 203 03
Sensitivity Low
Sensitivity High
90V~130V
180V~260V
97V~130V
194V~260V