Electrical installation
Important notes
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
Death or severe injuries when touching the power terminals.
ƒ
Protective measures:
Switch off the power supply and wait for at least three minutes before
ƒ
working on the power terminals.
Make sure that all power terminals are deenergised.
ƒ
{
Danger!
Hazardous electrical voltage
For the variants E84AZESxxxxxSDand E84AZESxxxxxLD the discharge current
to PE is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
Death or severe injuries when touching the device in case of a fault.
ƒ
Protective measures:
Implement the measures required in EN 61800−5−1, especially:
ƒ
– Fixed installation
– The PE connection must comply with the standards (PE conductor
diameter ³ 10 mm
56
2
or use a double PE conductor)
l
EDK84AZESRx DE/EN/FR/ES/IT 2.0