Mounting steps
Device size GG1 − GG3
Proceed as follows for installation:
1. Prepare M5 threaded holes on the mounting plate and equip them with screws and
washers.
– Two M5 screw and washer assemblies or M5 hexagon socket screws with washers
for the filter.
– Two M5 screw and washer assemblies or M5 hexagon socket screws with washers
for the standard device.
– Do not yet tighten the screws.
2. Remove the screw and washer assemblies from the filter to fix the standard device.
3. Mount the filter onto the prepared mounting plate.
– Only tighten the screws hand−tight.
4. Mount the standard device onto the prepared mounting plate.
– Observe the instructions in the documentation for the standard device.
– Only tighten the screws hand−tight.
5. If necessary, preassemble additional units.
6. Align all units.
7. Screw all units onto the mounting plate.
– Tightening torque: 3.4 Nm (30 lb−in)
EDK84AZESRx DE/EN/FR/ES/IT 2.0
Mechanical installation
Device size GG4 − GG5
E84AZESR008
l
Mounting variant
E84AZESR021
5
55