Electrical installation
Important notes
6
Electrical installation
6.1
Important notes
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
Danger!
Dangerous voltage
For the variants E84AZESRxxxxSD and E84AZESRxxxxLD the
discharge current to PE is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
42
Death or severe injuries when touching the power terminals.
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
Make sure that all power terminals are deenergised.
Death or severe injuries when touching the device in case of a
fault.
Implement the measures required in EN 61800-5-1, especially:
– Fixed installation
– The PE connection must comply with the standards (PE
conductor diameter ≥ 10 mm
2
or use a double PE conductor)
EDK84ZESR55 DE/EN/FR/ES/IT 2.0