Installation Of The Hob Fan - Kuppersbusch EKID9940.0 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 42
Instructions for assembly
Dimension in mm

Installation of the hob fan

• The product may only be connected by an authorised qualified
technician in compliance with applicable local regulations. The
same applies for the exhaust connections. The fitter is
responsible for perfect functioning at the installation location.
• When carrying out installation work, please observe the
relevant Building Regulations of the states and the energy
supply companies.
• The hob fan can be operated in the extraction air and
recirculation air mode.
• Lead the outgoing air outside through a ventilation shaft
intended for this purpose or through the wall of the building.
• The outgoing air may not be lead into a smoke or exhaust gas
chimney that is in use. If in doubt, please consult the district
master chimney sweep.
• If a fireplace requiring a chimney (coal, wood, oil or gas firing)
is used in the environment of the hob fan, you will need to
ensure that there is a sufficient supply of inlet air, otherwise a
risk of poisoning will arise. Operation of the hob fan will be safe
provided that the negative pressure caused by the hob fan
does not exceed 0.04 mbar (4 Pa) and that sufficient inlet air
can flow into the room.
• Exhaust air ducts must comply with fire class B 1 DIN 4102.
Please make sure that the minimum nominal diameter of the
appliance connections is not reduced.
• The Naber Compair Flow 150 system which is recommended
for the air flow and is compatible with the hob extractor should
always be used.
• The nominal diameter of the circulating air pipes may not be
less than 150 mm.
GB
39