Setting the torque limiter
The torque can be set to minimum, seeing as the appliance will give a maximum power thrust each
time it receives a movement command (only in the version LSO).
Position "Max" equals: 230Vac
Position "A" equals: 95 Vac
Position "B" equals: 70 Vac
Position "C" equals: 45 Vac
Position "MIN" equals: 20 Vac
Jumpers - selecting the second channel
If a two channel card is inserted, the second channel can be used as:
1) A gate blocking button by inserting the jumpers as shown in detail 1.
2) An N.O. (normally open) contact by inserting the jumpers as shown in detail 2.
Dett. 1
Important: When using a single channel receiver the jumpers must be positioned as shown in detail.
2
LOGIC CARD FUNCTIONS
Legend
PR:
Programming button
LPR:
Programming LED
D1:
Function selection dip-switch
LED: TB-FTCS-FTCI
Safety device status
Lit leds indicate safety devices at rest or jumped if
not used.
Leds off indicate that the safety devices are func-
tioning incorrectly (damaged), in the process of
intervening (working) or incorrectly jumped (unused
safety devices).
EXTRACTABLE LOGIC CARD FUNCTIONS
) Work time:
The gate is considered completely open (and therefore automatic reclosing is carried out) even when
the opening time has ended; program the opening times so as to leave a margin greater than the time
required to reach the opening travel limit FCA (or complete opening).
Never exceed a margin of 4 seconds.
2) Pause time:
Set the pause time according to the characteristics of the motor; if that time is very brief the gate will
carry out a rapid travel direction inversion as soon as it has reached the completely open position.
3) Electric lock activation time (overall)
anticipating motor activation
This is only active with an opening command and only when the gate moves from a almost completely
closed position.
Jumper
Dett. 2
CH2 RX
Command
TB
Jumper
output
Contact
N.O
TCS
D
LPR
3 2 1
ON
e limiter
A
PR
FTCI FTCS TB
PR
0-20 seconds
0-20 seconds
.3 seconds
0.3 seconds
5