Parameter Table - LOVATO ELECTRIC DMG700 Manuel D'application

Multimetre numerique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

– The following table lists the available sub-menus:
Code
Sub-menu
M01
GENERAL
M02
UTILITY
M03
PASSWORD
M04
INTEGRATION
M05
HOUR COUNTER
M06
TREND GRAPH
M07
COMMUNICATION (COMn)
M08
LIMIT THRESHOLDS (LIMn)
M09
ALARMS (ALAn)
M10
COUNTERS (CNTn)
M11
ENERGY PULSING (PULn)
M12
BOOLEAN LOGIC (BOOn)
M13
INPUTS (INPn)
M14
OUTPUTS (OUTn)
M15
USER PAGES (PAGn)
– Select the sub-menu and press
to show the parameters.
– Each parameter is shown with code, description and current setting value.
1 - Parameter code
2 - Parameter description
3 - Current setting value
4 - Selected parameter
– To modify the setting of one parameter, select it and then press
– If the Advanced level access code has not been entered, it will not be possible to enter editing page and an access denied message will be shown.
– If instead the access rights are confirmed, then the editing screen will be shown.
1 - Selected parameter
2 - Minimum possible setting
3 - Graph bar of the value-range
4 - New value entered
5 - Maximum possible setting
6 - Factory default setting
– When the editing screen is displayed, the parameter setting can be modified with L and M keys. The screen shows the new setting, a graphic bar that shows the setting range, the maximum and minimum
values, the previous setting and the factory default.
– Pressing simultaneously L and M, the setting is set to factory default.
– During the entry of a text string, keys L and M are used to select the alphanumeric character while
character selection straight to 'A'.
– Press MENU to go back to the parameter selection. The entered value is stored.
– Press MENU again to save all the settings and to quit the set-up menu. The multimeter executes a reset and returns to normal operation.
– If the user does not press any key for more than 2 minutes, the multimeter leaves the setu-p automatically and goes back to normal viewing.

PARAMETER TABLE

M01 - GENERAL
P01.01
CT primary
P01.02
CT secondary
P01.03
Rated voltage
P01.04
VT usage
P01.05
VT primary
P01.06
VT secondary
P01.07
Type of wiring
P01.01 – CT primary winding rated current.
P01.02 – CT secondary winding rated current. For DMG700 fixed to 5A.
P01.03 – System rated voltage. Leaving to Aut the multimeters automatically adapts bar-graph full scale.
P01.04 – Set to ON if VT are used. If set to OFF, the following two parameters will be ignored.
P01.05 – VT primary winding rated voltage.
P01.06 – VT secondary winding rated voltage.
P01.07 – Set this parameter according to the used wiring diagram. See wiring diagrams on last pages of the manual.
10
Description
Detailed data of the installation
Language, backlight, display pages, etc.
Access codes enabling
Readings integration time
Hour counter enabling
Trend graph reading and scale
Communication ports
Limit thresholds on readings
Alarm messages
General counters
Energy pulse count
Boolean logic variables
Digital inputs
Digital outputs
User-defined pages
.
is used to move the cursor along the text string. Pressing keys L and M simultaneously will move the
UdM
Default
Range
A
5
1-10000
A
5
V
Aut
Aut / 50-500000
OFF
OFF-ON
V
100
50-500000
V
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
G
B
5
L1-N