M07 - COMMUNICATION
P07.n.01 Serial node address
P07.n.02 Serial speed
P07.n.03 Data format
P07.n.04 Stop bits
P07.n.05 Protocol
P07.n.06 IP Address
P07.n.07 Subnet mask
P07.n.08 IP port
P07.n.09 Gateway function
P07.n.10 Client / server
P07.n.11 Remote IP address
P07.n.12 Remote IP port
P07.n.13 IP gateway address
Note: this menu is divided into 2 sections, for comm channels COM1..2
P07.n.01 – Serial address (node number) for the communication protocol.
P07.n.02 – Serial communication speed.
P07.n.03 – Data format. Can be set to 7 bits only for ASCII protocol.
P07.n.04 – Number of stop bits.
P07.n.05 – Communication protocol selection.
P07.n.06, P07.n.07, P07.n.08, P07.n.13 –TCP-IP coordinates for application with Ethernet interface. Not used for other types of interface modules.
P07.n.09 – Not supported function.
P07.n.10 – Enabling TCP-IP connection. Server = Awaits connection from a remote client. Client = Establishes a connection to the remote server.
P07.n.11, P07.n.12 – Coordinates for the connection to the remote server when P07.n.10 is set to Client.
M08 - LIMIT TRESHOLDS
P08.n.01 Reference measurement
P08.n.02 Function
P08.n.03 Upper threshold
P08.n.04 Multiplier
P08.n.05 Delay
P08.n.06 Lower threshold
P08.n.07 Multiplier
P08.n.08 Delay
P08.n.09 Normal status
P08.n.10 Latch
Note: This menu is divided into 8 sections, for limit thresholds LIM1..8
P08.n.01 – Defines which measurements of the multimeter must be compared with limits.
P08.n.02 – Function of the limit threshold.
It can be:
Max = LIMn active when the measurement is higher than P08.n.03. P08.n.06 is the reset threshold.
Min = LIMn active when the measurement is lower than P08.n.06. P08.n.03 is the reset threshold.
Min+Max = LIMn active when the measurement is higher than P08.n.03 or is lower than P08.n.06.
P08.n.03 and P08.n.04 – Used to define the upper threshold, that is made up by the value set in P08.n.03 multiplied by P08.n.04.
P08.n.05 – Trip delay on upper threshold.
P08.n.06, P08.n.07, P08.n.08 – Like above, referred to lower threshold.
P08.n.09 – Allows to invert the status of the limit LIMn.
P08.n.10 – Defines if the threshold remains latched and thus needs to be reset manually (ON) or if it resets automatically (OFF).
M09 - ALARMS
P09.n.01 Alarm source
P09.n.02 Channel number (x)
P09.n.03 Latch
P09.n.04 Priority
P09.n.05 Text
Note: This menu is divided into 8 sections, for alarms ALA1..8
P09.n.01 – Signal that generates the alarm. It can be the overcoming of a limit threshold (LIMx), the activation of an external alarm (INPx), one Boolean logic condition (BOOx).
P09.n.02 – Channel number (x) referred to the previous parameter.
P09.n.03 – Defines if the alarm remains latched and has to be reset manually (ON) or if it automatically resets (OFF).
P09.n.04 – If the alarm has high priority, when it is activated the display page automatically switches on the alarm page, and the alarm is shown with the Warning icon. If instead the priority level is low, the page does
not change and shown with the information icon.
P09.n.05 – Free text of the alarm. Max 16 characters.
12
UdM
Default
Range
01
01-255
bps
9600
19200
38400
57600
115200
8 bit - n
8 bit, no parity
8bit, odd
8 bit, even
7 bit, odd
7 bit, even
1
Modbus RTU
Modbus RTU
Modbus ASCII
Modbus TCP
000.000.000.000
000.000.000.000 -
255.255.255.255
000.000.000.000
000.000.000.000 -
255.255.255.255
1001
0-9999
OFF
OFF/ON
Server
Client / Server
000.000.000.000
000.000.000.000 –
255.255.255.255
1001
0-9999
000.000.000.000
000.000.000.000 –
255.255.255.255
UdM
Default
Range
OFF
OFF- (measures)
Max
Max - Min - Min+Max
0
-9999 - +9999
x1
/100 - x10k
sec
0
0.0 - 600.0
0
-9999 - +9999
x1
/100 - x10k
sec
0
0.0 - 600.0
OFF
OFF-ON
OFF
OFF-ON
Default
Range
OFF
OFF-LIMx-INPx-BOOx
1
OFF
OFF-ON
Low
Low - High
ALAn
(Text - 16 char)
1200
2400
4800
G
9600
B
1-2
1-8