LOVATO ELECTRIC DMG700 Manuel D'application page 11

Multimetre numerique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

M02 - UTILITY
P02.01
Language
P02.02
Display contrast
P02.03
High backlight level
P02.04
Low backlight level
P02.05
Low backlight delay
P02.06
Default page return
P02.07
Default page
P02.08
Default sub-page
P02.09
Display update time
P02.06 – If set to OFF the display always remains in the page where the user left it. If set to a time delay, after that time the display page goes back to page set in P02.07.
P02.07 – Number of the page to which the display returns automatically after time specified by P02.06 has elapsed from the last keystroke.
P02.08 – Sub-page type to which the display returns after P02.06 has elapsed.
M03 - PASSWORD
P03.01
Enable passwords
P03.02
User level password
P03.03
Advanced level password
P03.01 – If set to OFF, password management is disabled and the access to setup parameters and command menu is allowed.
P03.02 – When P.03.01 enabled, value to be specified to get user access. Refer to Password Access chapter.
P03.03 – Like P03.02, but referred to advanced access.
M04 - INTEGRATION
P04.01
Integration mode
P04.02
Power integration time
P04.03
Current integration time
P04.04
Voltage integration time
P04.05
Frequency integration time
P04.01 – Selection of average reading calculation method:
Fixed = Readings are integrated for the set time. Every time the integration time elapses, the Average value is updated with the result of the last integration.
Shift = The instantaneous values are integrated for a period of time equal to 1/15th of the set time. Every time this interval elapses, the oldest value is replaced with the new one just calculated. The average value is
updated every 1/15th of the time set, considering a time-sliding window that groups the last 15 calculated values, with a total length equal to integration time setting.
Sync = Like fixed mode, but the integration intervals are started by an external digital input programmed with Synchronisation function.
Bus = Like fixed mode, but the integration intervals are started by synchronising messages on the serial bus.
P04.02 – Average readings integration time, used for active, reactive and apparent power.
P04.03, P04.04, P04.05 – Readings integration time (AVG) for the corresponding measurements.
M05 - HOUR COUNTER
P05.01
Hour counter enable
P05.02
Partial hour counter enable
P05.03
Channel number (x)
P05.01 – If set to OFF the hour counters are disabled and the hour meter page is not shown.
P05.02 – If set to OFF, the partial hour counter is not incremented. If ON, time is incremented as long as DMG is powered. If set to an internal variable (INPx-LIMx-BOOx), time increments only while a programmed
condition occurs.
P05.03 – Number of the channel (x) of the variable eventually used in the previous parameter. Example: If the partial hour counter must count the time during which one measurement is above a certain threshold, e.g.
defined by LIM3, then it is necessary to program LIMx in the previous parameter and channel 3 in this parameter.
M06 - TREND GRAPH
P06.01
Trend graph measurement
P06.02
Autorange
P06.03
Full scale value
P06.04
Full scale multiplier
P06.01 – Selects the reading to be shown on trend graph page.
P06.02 – Choice between automatic range or fixed range defined by the user.
P06.03 – Full scale range value. The unit of measure is the one defined by the selected reading.
P06.04 – Full scale value multiplier.
UdM
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
%
50
0-100
%
100
0-100
%
30
sec
30
5-600
sec
60
OFF / 10-600
VL-L
VL-L / VL-N ...
INST
INST / HI / LO /
AVG / MD /GRAPH /
sec
0.5
0.1 - 5.0
UdM
Default
Range
OFF
OFF-ON
1000
0-9999
2000
0-9999
UdM
Default
Range
Shift
Fixed / Shift
Sync. / Bus
min
15
min
15
min
1
min
1
UdM
Default
Range
ON
OFF-ON
ON
OFF-ON- INPx-
LIMx-BOOx
1
UdM
Default
Range
kW (tot)
VL-L (eq) AVG
AVG
kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
G
B
0-50
1-8
1-60
1-60
1-60
1-60
1-8
11