Connecting IntelliChlor to an SunTouch System
To connect the four wire communication cable from the IntelliChlor Power Center (see page 29) to the
motherboard located in the SunTouch Power Center:
WARNING - Switch OFF main system power to the SunTouch Power Center before making
any connections.
To access the SunTouch Power Center electronics compartment:
1. Unlatch the front door of the SunTouch Power Center, and open the door.
2. Loosen the retaining screw on front panel. Open the hinged front panel to access the electronics
compartment.
3. Route the four conductor cable up through the Power Center grommet opening located on the left
side, and up through the low voltage raceway to the motherboard.
4. Strip back the cable conductors ¼ in. Insert the wires into the screw terminals (provided in the kit).
Secure the wires with the screws. Make sure to match the color coding of the wires; Red = +15,
Yellow = +DT, Green = -DT, and GND = Black.
5. Insert the connector on the COM-PORT (J11) screw terminal on the motherboard.
6. When the connection is completed, close the control panel and secure it with the retaining screw.
7. Close the front door. Fasten the spring latch.
COM PORT
Wiring AC Power from IntelliChlor (SCG) and IntelliFlo pump to

IntelliTouch, EasyTouch and SunTouch Automation Control System

(see page 29 for diagram)
IntelliChlor (SCG) AC Wiring Instructions: When using the IntelliChlor salt chlorine generator and an
IntelliFlo pump (or 2-speed pump) with a Pentair Water Pool and Spa
SunTouch® automation control system , the IntelliChlor AC power center wires must be connected to the
PUMP SIDE OF THE MAIN FILTER PUMP RELAY located in the load/power center (see page 29 for diagram).
This ensures that the IntelliChlor cell produces chlorine only when the main filter pump is on. This method
does not require a ground fault circuit-interrupter (GFCI) to protect the circuit. Note: For non-automation
systems using a time clock, see page 33 for wiring information.
IntelliChlor Electronic Chlorine Generator Installation and User's Guide