Dimensioning
5.1
Important notes
(
Stop!
Thermal overload of brake chopper EMB9352 or of the brake
resistor.
If the value falls below the brake resistance R
maximum running time of the brake chopper / brake resistor is
exceeded, the components will be overloaded.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
ƒ
Brake
resistance R
76
The components fail.
Always implement the temperature monitoring of the brake
resistor into the emergency stop chain.
Please observe the running time t
brake resistor and the brake chopper.
Calculate the generated braking energy of the application for
brake resistances <R
– Connect the brake chopper in parallel if the maximum values
of the brake chopper are exceeded.
EMB9352
U
= 375 V
U
= 725 V
ch
ch
U
= 765 V
ch
= 27 W R
= 54 W
R
B,lim
B,lim
<27 W
<54 W
B
³27 W
³54 W
and dead time t
on
. (¶ 79)
B,lim
Dimensioning steps
1. Calculate running time and dead time. (
– Condition "t
+ t
on
2. Dimension brake chopper and brake resistor .
^
(
79)
1. Calculate running time and dead time. (
– The technical data of the brake resistor must be
observed.
l
or if the
B,min
of the
off
^
77)
= 3 s" must be observed.
off
^
77)