For proper operation of the battery management, the following data must be set during first connection:
Data
Comment
This name is associated to a logo displayed on the main page
Name
Battery type
The battery type shall be selected. Full charge detection, critical
state of charge and deep discharge levels are set according to
battery type.
Nominal
The nominal capacity of the battery should only be adjusted
1
capacity
when the batteries are 100% charged.
Factory setting is 98%. The CEF is automatically adjusted by
Charge efficiency
1
battery management averaging over the last 4 cycles.
factor (CEF)
Set the rated voltage 12 or 24V of the battery group so that the
Nominal voltage
capacity calculation can be done properly.
1
Factory setting set to 30%.
Cycle depth
Alarm capacity
User capacity alarm level : factory setting to 50 %. This level has
no relation with Capacity Off Level field available into Relay
settings (see section 4.2.1).
1
Factory setting according to battery type.
Peukert factor
Overvoltage alarm threshold (+1). Factory setting for the alarm
Overvoltage
Level
threshold is 15.0 V.
Serial number of the shunt, software and hardware version.
Shunt
This name is associated to a logo displayed on the main page
Name 2
Battery 2
Overvoltage alarm threshold. Factory setting for the alarm
Overvoltage
threshold is 15.0 V.
Factory setting for the alarm threshold is 11.5 V.
Battery 2
Undervoltage
1
See terms and definition in section 5.3
Additional battery at terminal (+2)
Range
Start Stb, Start port,
Starter, Aux, Bow,
House, House I, House II
GEL, AGM, Open Lead,
Lithium
1-9999Ah
1-100%
12V/24V
10-90%
1-100%
1.00-1.50
0-32V
-
Start Stb, Start port,
Starter, Aux, Bow,
House, House I, House II
0-32V
10-26V