Stop Input
This menu permits to select the functions associated to the
command of STOP.
no
The input STOP is not available.
ProS
The input STOP stops the gate: pressing the command START
inuE
the gate continues the motion.
The command STOP stops the gate: at the next START the
gate starts moving in the opposite direction.
The setting of parameter STOP determines also in which direction the
gate will move at the next START, if it has stopped because of an
intervention of the safety edges or the obstacle sensor. If you set no, the
START command restarts the motion in the same direction.
NOTE: during the pause, the STOP command will stop the pause time
count, the next START command will always close the gate.
Exterior photocell input
This menu makes it possible to enable the exterior photocell input, i.e.
inactive during opening (see the section regarding installation).
no
Input disabled (ignored by the control unit).
No jumper with the common is required.
CF.Ch
Input enabled even at standstill gate too: the opening
movement does not start if photocell is interrupted.
Ch
Input enabled for the closing phase only.
Warning: if you select this option, you must disable
photocell test.
Interior photocell input
This menu makes it possible to enable the interior photocell input, i.e.
active during opening and closing (see the section regarding installation).
no
Input disabled (ignored by the control unit).
AP.Ch
No jumper with the common is required.
Input enabled.
Test of the photocells
In order to achieve a safer operation for the user, the unit performs a
photocells operational test, before a normal working cycle.
If no operational faults are found, the gate starts moving.
Otherwise, it will stand still and the flashing light will stay onfor 5 sec.
The whole test cycle lasts less than one second.
WARNING: V2 suggests to keep activated the test of the
photocells in order to grant a higher safety of the system.