This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase.
ChiU
the gate starts closing
no
command is ignored
PAUS
The pause time is reset (
ChiU
no
Select option
, to set up the "step-by-step" operation logic.
Select option
, to set up the "always open" operation logic.
ATTENTION: Apart from selected option, the start command
lets the gate close if it has been stopped by a stop command or if
the automatic closing was not enabled.
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
PAUS
The gate stops and goes to pause
ChiU
the gate immediately starts closing
no
the gate goes on with the opening phase (command is ignored)
WARNING: a Start command in any phase of partial opening
will cause the total opening; the Start Pedestrian command is
always ignored during a total opening.

Automatic closing

In automatic mode, the control unit automatically recloses the gate on
expiry of the time limit set in this menu.
The Start command, if enabled by
before the set up time expires.
In semi-automatic operation, that is to say, if the automatic closing
function is disabled by setting the value to zero (
St.PA
the gate can be closed through the start command only: in this case,
menu setup will be ignored.
If the control unit receives a Stop command when the gate is in pause,
it will automatically pass to the semi-automatic operation.
Closing after transit
During the automatic operation, the pause count down starts from the
set up value each time a photocell operates during the pause.
If the photocell operates during the opening time, this time will be
immediately stored as pause time.
This function allows having a fast closing as soon as transit through the
gate is completed, therefore, a time shorter than
Ch.AU
no
used.
will be used when
As for semi-automatic operation, this function is not active.
68
Ch.AU
)
St.PA
menu, allows closing the gate
no
will be displayed),
Ch.AU
is generally
is set up.