Braking
In the final section of the trip, the control unit drives the motor at
reduced power, depending on the values set for parameters
Po.r2
.
In this menu, it is possible to adjust the duration of the braking phase.
The value set is the percentage of the total trip, and is equal for both
motors during opening and closing.
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase.
PAUS
The gate stops and goes to pause.
ChiU
The gate immediately starts closing.
no
The gate go on with the opening phase (command is ignored).
PAUS
no
Select option
, to set up the "step-by-step" operation logic.
Select option
, to set up the 'always open' operation logic
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase.
StoP
The gate stops and its cycle is considered as finished.
APEr
The gate opens again.
StoP
APEr
Select option
, to set up the "step-by-step" operation logic.
Select option
, to set up the 'always open' operation logic.