Air Regulation - Lamborghini Caloreclima 55 PM/2-E Manuel D'installation Et D'entretien

Bruleurs a gaz a deux flammes
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

AIR REGULATION

With PM/2 -E type burners, the air flap is activated by an electric servo control. The air flap positions are
determined by means of the cams, with their alignment indicated on the reference disc.
The cams can be moved by using the equipped wrench as they are self-locking.
By pressing button B , the air flap drive system is disengaged, and the air flap is free to be moved manually.
CALIBRATION SQN 30.111
Release button
Cams
I
Max air opening
II
Air closing on stopping
III Air opening on start-up or 1st stage
IV Opening valve SKP...
B
Reference disc
54
Wrench