Operating Instructions Enabling Switch ZSE
Correct use
The EUCHNER enabling switch is a manually
operated command switch, which allows work to
be carried out in the danger area of automated
production systems in manual operating mode.
This mode must be secured with a lockable selector
switch according to EN 60204, part 1.
The enabling switch must be logically gated with
the machine control system in a manner that
ensures compliance with the requirements
applicable to safety circuits according to VDI 2854
and/or EN ISO 10218-1. Under the conditions
specified therein, the enabling signal may cancel
the protective action of moving safety guards.
Authorized operating personnel may then enter the
danger area:
for setting up
for observing work sequences
for maintenance.
Important:
The user is responsible for the integration of the
device in a safe overall system. For this purpose
the overall system must be validated, e.g. in
accordance with EN ISO 13849-2.
If the simplified method according to section 6.3
EN ISO 13849-1:2008 is used for validation, the
Performance Level (PL) may be reduced if several
devices are connected one after the other.
The enabling switch user must assess and
document remaining risks.
If a product data sheet is included with the
product, the information on the data sheet applies
in case of discrepancies with the operating
instructions.
Incorrect use
The enabling signal must not be simulated by fixing
the switching contact in stage 2.
Function
Stage 1: Off function, pushbutton not pressed
Stage 2: Enabling function, pushbutton pressed to
center position (actuating point)
Stage 3: Positively driven Off function, pushbutton
pushed to end stop
The enabling function is cancelled by releasing the
pushbutton or pressing it beyond the actuating
point. The enabling function does not reactivate
when returning from stage 3 to stage 1. For
information on the functions of the various versions,
see Figure 1.
Safety precautions
Enabling switches fulfill a personal protection
function. Incorrect use or tampering can lead to
severe injuries to personnel.
All the safety and accident prevention
regulations for the specific application, e.g.
guidelines of the employers liability insurance
associations, safety requirements of the VDI
(EN ISO 10218-1, VDI 2854), EN 60204,
EN 12100, EN ISO 13849, EN 61062,
DIN VDE 0106 part 100, etc., must be
observed.
Electromechanical enabling switches/devices
are to be logically gated with the control
system in a manner that ensures compliance
with the requirements applicable to safety
circuits according to EN ISO 10218-1, DIN EN
60204-1, EN ISO 13849-1, DIN EN ISO 11161
and VDI 2854.
No commands for potentially hazardous
conditions are allowed to be initiated with
enabling switches alone.
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49 711 7597-0 Fax +49 711 753316 www.euchner.de info@euchner.de
The safety function of enabling switches must
not be bypassed (bridging of contacts),
manipulated or otherwise rendered ineffective.
The enabling switch must be protected against
attempts by the operator to bypass its
function.
Enabling switches may be used only by
authorized persons who can recognize hazards
in time and who are able to take appropriate
action immediately.
Every person present in the danger area must
carry his/her own enabling switch on his/her
person.
Mounting, electrical connection and setup only
by authorized personnel.
Mounting
The enabling switch must be fitted in a suitable
housing.
Slide enabling switch without protective cap
through the front panel cut-out from the rear.
Screw protective cap onto the front of the
enabling switch to the stop.
During installation it must be ensured that all three
switch positions can be reached unhindered.
The switch must be securely fastened, but must
not be placed under stress by the fastening.
The device must be installed so that tampering
is not possible by simple mechanical measures
(clamping, adhesive tape, etc.).
Electrical connection
In the installation of a system, the cables and
wires used (except earth conductors) that can
be touched without opening or removing a
cover, or are laid on conductive parts external
to the device, must be either double insulated
or have reinforced insulation between core and
surface, or be surrounded by a metal sheath
of adequate current-carrying capacity in case
of a short between core and sheath.
At voltages > AC 50 V / > DC 120 V fit
insulating sleeves to the spare tab connectors.
Hazards due to crushing or cutting of the
connection cable must be prevented by suitable
measures:
Protecting the cable by laying it appropriately,
e.g. in a protective sleeve.
Monitoring short circuits using an evaluation unit.
Using cable with individually screened cores. The-
se screens are to be connected to the machine
or plant earthing system. In this way cable short
circuits can be detected and the control system
shut down immediately by the triggering of the
short circuit protection.
Setup
Check the enabling switch (enabling function at
stage 2, and positively driven at stage 3) by
performing a functional check.
Service and inspection
No servicing is required, but to ensure trouble-free
long-term operation, regular inspection of the
electrical and mechanical function is required.
In the event of functional faults or damage,
the enabling switch must be replaced. Repairs
are only to be made by the manufacturer!
Note: The year of manufacture can be seen in the
bottom, right corner of the rating plate.
Exclusion of liability under the following
circumstances
incorrect use
non-compliance with safety regulations
electrical connection not performed by authorized
personnel
function tests not performed
EC declaration of conformity
The manufacturer named below herewith declares
that the product fulfills the provisions of the
directive(s) listed below and that the related
standards have been applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives and standards applied:
- Machinery directive 2006/42/EC
- EMC directive 2004/108/EC
- EN 60947-5-8:2006
- EN 61000-4-3:2006 + A1:2008 + A2:2010
- EN 61000-4-6:2009
Leinfelden, March 2013
Dipl.-Ing. Stefan Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.

Technical data

Parameters
Value
Housing material
Plastic, color black
Protective cap material
CR, color black
Weight
Approx. 100 g
Degree of protection
front IP65
according to IEC 60529
connections IP00
Mechanical life min.
Position 1-2-1
1x10
5
cycles
Position 1-2-3-1
1x10
5
cycles
Ambient temperature
-5 ... +60 °C
Degree of contamination
(external, acc. to
3 (industrial)
EN 60947-1)
Installation position
Any
Impact strength
> 100 N
Switching elements
See Figure 1
Switching principle
Slow-action contact element
Connection
Tab connector 2.8 x 0.8 according
to IEC 760
ZSE2-3 and ZSE2-4
Switching element E3 soldered
connection
Rated impulse
U
= 2.5 kV
imp
withstand voltage
Rated
U
= 250 V
i
insulation voltage
Rated short-circuit current
100 A
Utilization category
AC-15 4 A 230 V
According to EN 60947-5-1
DC-13 3 A
Switching current, min.
1 mA
, at 24 V
Switching voltage, min.
12 V
at 10 mA
Short-circuit protection
4 A gG
Reliability figures acc. to EN ISO 13849-1
B
5 x 10
5
10d
24 V