Operating Instructions
Safety Switch TP...
Notes about
The following information applies to devices
with cable entry:
For use and application as per the requirements
of
a copper wire for the temperature range
60/75 °C must be used.
The following information applies to devices
with plug connector:
This device is intended to be used and applied with
a Class 2 power source in accordance with UL1310.
Connecting cables for safety switches installed at
the place of use must be separated from all moving
and permanently installed cables and un-insulated
active elements of other parts of the system that
operate at a voltage of over 150  V. A constant
clearance of 50.8  mm must be maintained. This
does not apply if the moving cables are equipped
with suitable insulation materials that possess an
identical or higher dielectric strength compared to
the other relevant parts of the system.

EU declaration of conformity

The declaration of conformity is part of the oper-
ating instructions, and it is included as a separate
sheet with the unit.
The original EU declaration of conformity can also
be found at: www.euchner.com
Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Germany
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com

Technical data

Parameter
Value
Housing material
Reinforced thermoplastic
Degree of protection
acc. to IEC 60529
Cable entry
IP67
Plug connector SR6/SR11
IP65
Mechanical life
1 x 10
operating cycles
6
Ambient temperature
-20 ... +55 °C
Degree of contamination
3 (industrial)
(external, acc. to EN 60947-1)
Installation orientation
Any
Approach speed, max.
20 m/min
Extraction force (not locked)
20 N
Retention force
10 N
Actuating force, max.
10 N
Actuation frequency
1,200/h
Switching principle
Slow-action switching contact
Contact material
Silver alloy, gold flashed
Connection
TP...
Cable entry
TP...SR6
Plug connector SR6, 6-pin+PE (PE
not connected)
TP...SR11
Plug connector SR11, 11-pin+PE
(PE not connected)
Conductor cross-section
0.34 ... 1.5 mm²
(flexible/rigid)
Operating voltage for optional
L024 24 V
LED indicator
Rated insulation voltage
TP..., TP...SR6
U
= 250 V
i
TP...SR11
U
= 50 V
i
Rated impulse withstand voltage
TP..., TP...SR6
U
= 2.5 kV
imp
TP...SR11
U
= 1.5 kV
imp
Conditional short-circuit
100 A
current
Switching voltage, min.,
12 V
at 10 mA
Utilization category acc. to EN 60947-5-1
TP..., TP...SR6
AC-15 4 A 230 V /
DC-13 4 A 24 V
TP...SR11
AC-15 4 A 50 V /
DC-13 4 A 24 V
Switching current, min.,
1 mA
at 24 V
Short circuit protection
(control circuit fuse)
4 A gG
acc. to IEC 60269-1
Convent. thermal current I
4 A
th
Solenoid operating voltage/solenoid power consumption
TP...024
AC/DC 24 V (+10%/-15%) 8 W
TP...048
AC/DC 48 V (+10%/-15%) 8 W
TP...110
AC
110 V (+10%/-15%) 10 W
TP...230
AC
230 V (+10%/-15%) 11 W
Duty cycle
100%
Locking force F
max
TP1/TP2/TP3/TP4
F
= 1,300 N
max
TP5/TP6
F
= 800 N
max
F
Locking force F
max
Zh
(F
=
)
Zh
acc. to EN ISO 14119
1.3
TP1/TP2/TP3/TP4
F
= 1,000 N
Zh
TP5/TP6
F
= 600 N
Zh
Reliability values acc. to EN ISO 13849-1
B
3 x 10
10D
6
at DC-13 100 mA / 24 V
8