Coding by setting the DIP switches
Remove the front plate of the CAN addressing module in order to set the baud rate and the
controller address in its interior with DIP switches.
Left DIP switch
(S1L, S2L, S3L, S4L, S5L)
Setting the baud rate
Set the baud rate with the switches S1L, S2L and S3L. The switch settings required for setting
the baud rate are represented in the following table:
Baud rate
[kbaud]
500
250
125
1000
Setting the controller address
The switches S4L and S5L as well as the switches S1R to S4R correspond to certain values:
S4L
Value
1
In order to set the controller address, add up the values in a way that their sum equals the
controller address. Then set those switches to "ON" whose values you have added up.
Example:
Setting the controller address 27
The sum of the values has to equal 27: 1 + 2 + 8 + 16 = 27
ð Switch setting:
S4L
S5L
ON
ON
Having set baud rate and controller address, fasten the front plate to the CAN addressing
module.
EDK2174DB DE/EN/FR 4.0
Preliminary works
Coding by setting the DIP switches
S1L
OFF
ON
OFF
50
ON
OFF
S5L
S1R
2
S1R
OFF
Right DIP switch
(S1R, S2R, S3R, S4R, S5R)
S2L
OFF
OFF
ON
ON
OFF
S2R
4
8
S2R
S3R
ON
ON
10
S3L
OFF
OFF
OFF
OFF
ON
S3R
S4R
16
32
S4R
OFF
l
2174CAN005