Wiring Details - WIKA IS-20-S Mode D'emploi

Transmetteur de pression
Masquer les pouces Voir aussi pour IS-20-S:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. Starting, operation
With a line transformer you realise the mandatory galvanic isolation of the voltage and
current supply between hazardous and non-hazardous areas and ensure the safety
connection data.

Wiring details

L-Connector
DIN 175301-803 A
2-wire
U+ = 1 U- = 2
Cable screen
Wire gauge
up to max. 1.5 mm
2
6 to 8 mm
Diamter of cable
ship approval:
10 to 14 mm
Ingress Protection
IP 65
per IEC 60 529
The ingress protection classes specified only apply while the pressure transmitter is
connected with female connectors that provide the corresponding ingress protection.
12
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
CIrcular connector
Flying leads,
M12x1, 4-pin
1.5 m
U+ = 1 U- = 3
U+ = brown U- = green
PUR-cable: grey
FEP-cable: twisted and tinned
-
0.5 mm
2
(AWG 20)
6.8 mm (Code DL / EM)
-
7.5 mm (Code DM)
IP 67 - Order code: DL
IP 67
IP 68 zero/span not adjustable-
Order code: EM / DM
GB
7. Starting, operation
Wiring details
Bayonet connector, 6-pin
2-wire
U+ = A U- = B
Ingress Protection
IP 65 (NEMA 4)
per IEC 60 529
The ingress protection classes specified only apply while the pressure transmitter is
connected with female connectors that provide the corresponding ingress protection.
Model IS-20-F, IS-21-F, IS-20-H with field case:
Cable connection in the spring clip terminal
Cover the stripped wire ends with end splices.
Unscrew the case cover.
Loosen the cable gland using an open-end
wrench, wrench size 24.
Lead the cable through the cable gland into
the opened case head.
Press the corresponding plastic lever at the
spring clip terminal down using a screw driver,
so that the clamped contact will be released.
Lead the prepared flying lead into the opening
and let go of the plastic lever, so that the flying
lead will be squeezed inside the spring clip
terminal.
After connecting the individual wires, tighten
the cable gland and screw down the case
over.
IS-2X
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
GB
Field case (with internal spring clip terminals)
U+ = 1 U- = 2
Test+ = 3 Test- = 4 Screen = 5
IP 67
Function of the test circuit
for 2-wire:
By means of the test circuit the current
can be metered during normal opera-
tion without having to disconnect the
instrument. For that purpose you have
to connect an ammeter (for appli-
cations in hazardous areas; internal
resistance < 15 Ohm) to the test
+/- terminals.
13
IS-2X

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Is-21-sIs-20-fIs-21-fIs-20-h

Table des Matières